Energy integration · 27 August 2025

Medium Voltage in the BMS: IEC 60870-5-104 or IEC 61850?

Medium voltage is not usually in BMS scope. In data centers, skipping it leaves blind spots, and read-only telemetry in Niagara closes them safely.

Medium voltage (MV) is not usually in BMS scope. But in integrated sites like data centers, skipping it creates blind spots for uptime, incident response and energy reporting. The pragmatic move is read-only MV telemetry in Tridium Niagara: one pane of glass for HVAC and power, while protection stays firmly in the electrical domain.

Why add MV to Niagara

IEC 60870-5-104

Lean, robust telecontrol over TCP/IP, port 2404. It is ideal when MV data comes through RTUs – Remote Terminal Units, field aggregators that collect signals from MV gear and publish them northbound. You get spontaneous events, general and counter interrogations, sequence and flow control, timestamps and quality, mapped to a straightforward points model that drops neatly into Niagara alarms and trends. A good fit when your MV package already exposes a SCADA-style point list.

IEC 61850 MMS

A protocol for IEDs – Intelligent Electronic Devices for protection, metering and control at the bay or feeder. It carries a self-describing substation model (logical devices and nodes, data objects and attributes) over MMS, port 102. Niagara can discover the model automatically and read breaker states, protection alarms, sequence of events and measurements with clear semantics, for example XCBR, MMXU, PTOC and GGIO. Vendor-neutral, consistently named, and kept strictly read-only on the BMS side.

How to choose

Building data centers or campus substations on Niagara? Let MV telemetry live in your BMS, safely. See our IEC 60870-5-104 and IEC 61850 MMS drivers, and for metering, the DLMS/COSEM driver. We are happy to do a quick fit check.