Case study · 5 October 2026

What Modbus Can't See: Reading ION Waveform Records in Niagara

A client suspected problems with the incoming power supply. The meters had recorded every blip, but Modbus could not show them.

A few weeks ago an integrator asked us for a trial of our Schneider ION driver. His client suspected problems with the incoming power supply. The site has a Niagara Supervisor and ION7650 meters on both incoming supplies, already connected over Modbus. What he wanted was to see any voltage or frequency blips in the meters’ waveforms.

What Modbus cannot do

Modbus reads the meter’s live values, not its waveform recordings. And the meters do record them: ION meters have waveform recorders that capture the voltage and current signal up to 30,000 times a second, starting a few cycles before a disturbance, and keep the records in memory. Getting at them needs the native ION protocol.

The same afternoon

We sent the driver and a demo license within the hour. By mid-afternoon he had pulled the histories from both meters into Niagara, and they quickly showed there had been no abnormal power blips. He put the results into a report for the client, which also showed what the driver could do.

The client received the trial positively and decided to keep it. The PO came in the following week, the license went out the same day, and a few days later the driver was installed and licensed on the Supervisor.

Less than two weeks from the first email to a licensed driver, with the technical question answered on day one. Request, trial, test, PO – wouldn’t it be wonderful if the entire industry worked like that?

Check your own meters

If you have ION meters connected over Modbus, it is worth knowing how much more they record than the register map shows: waveforms, data recorder histories and event logs. Our ION driver for Niagara 4 reads them natively, and the trial is the full driver, so you can check it against your own meters. Send us your Niagara Host ID and we will set it up.